GRAND DECHO GDD-400GFK diesel generator sets, relying on many years of market experience, integration of advanced technology at home and abroad, and through rigorous development and verification, to ensure the unit's high reliability, high efficiency, environmental protection and low maintenance costs. The unit adopts mature control system, which can meet the individual power needs of different users.
Generator Set Parameters
Model GDD-400GFK
Rated Power 400kW/500kVA
Rated Voltage 400V
Rated Current 722A
Frequency 50Hz
Power Factor -0.8
Electrical Efficiency .≥33.2%
Fuel Consumption ≤103 L/kW.h
Starting Method Electric
Weight 2842kg
Engine Parameter
Engine Model YC6K660-D30
Type ..........................Vertical,Six-cylinder,Four-stroke,Water-cooled,
Direct injection,Electric starter
Type of Inlet Pressurised, air-to-air intercooling
Bore×Stroke (mm×mm) 6-129×165
Displacement(L) 12.94
Compression Ratio 17.5 : 1
Max.Output(kW/rpm) 490 / 1500
Rated Output(kW/rpm) 441 / 1500
Fuel Consumption(g/kW/h) ≤195
Oil Consumption(g/kW/h) ≤0.441
Speed Control Mode Electric
Oil Capacity(L) 34
Overhaul Time(h) >1000
Inlet Exhaust Parameters
-Clean air filter 3.5 kPa
-Dirty air filter 5 kPa
-Intake Resistance Alarm Values 6.2 kPa
-Air Filter Form Dry Paper Cartridge
Max.Exhaust Back Pressure 10 kPa
Exhaust Port Inner Diameter Φ 125 mm
Generator Parameters
Generator Model Evotec TCU318C
Wiring Method.................................Three-phase Four-wire (Y type)
Voltage Regulating Mode AVR
Heat Balance Parameters
Total Fuel Chemical Energy (kW) 1153 ,1022
Output Power (Gross) (kW) 490, 441
Output Power (Net) (kW) 470, 421
Fan Power Consumption (kW) 18.7 ,18.7
Other Power Losses (kW) 1,1
Coolant Heat Dissipation (kW) 208 ,196
Intake Intercooler Heat Sink (kW) 123 ,108
Exhaust Air Heat Dissipation (kW) 292 ,241
Heat Radiation (kW) 39 ,35
Cooling Parameters
Total Coolant Capacity —— L
Engine Coolant Capacity 20 L
Radiator Coolant Capacity —— L
Line Coolant Capacity —— L
Maxengine Water Temperature. 93℃
Thermostat Operating Temperature
Nitial Opening Temperature(75±2)℃,Opening Temperature<85℃
-Standby Power 8.0℃
-Prime Power 7.6 ℃
Test Conditions
Ambient Temperature 25 ℃
Atmospheric Pressure. 100 kPa
Relative Humidity 30 %
Intake Resistance At Maximum Operating Conditions ≤5 kPa
Exhaust back Pressure Limits ≤10 kPa
Fuel Temperature (feed pump) 38±2 ℃

Copy product links